Issue Date: August 23, 1999
Revision Date: March 10, 2000
 

Caldwell Systems Corp.

Tank Manager Liquid Sensor, Version TMLIQ

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:           

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

ultrasonic

Test Results:

Horizontal Position

unleaded gasoline

diesel

water

Response time (sec)

<1

<1

<1

Recovery time (sec)

<1

<1

<1

Lower detection limit (cm)

1.28

1.30

2.43

Precision - standard deviation (cm)

0.05

0.06

0.25

Vertical Position

 

 

 

Response time (sec)

<1

<1

<1

Recovery time (sec)

<1

<1

<1

Lower detection limit (cm)

8.56

7.59

9.27

Precision - standard deviation (cm)

0.22

0.11

0.44

Specificity Results:
Evaluator claims sensor will detect fuels or other liquids.

Comments:
Sensor is designed to alarm only when liquid is present from one end of sensor to the other.  Therefore, sensor orientation (vertical or horizontal) will effect lower detection limit.
Sensors are reusable.

 

Caldwell Systems Corp.

Evaluator:  Ken Wilcox Associates

600 South Sunset Street, Unit D

Tel:  (816) 443-2494

Longmont, CO 80501

Date of Evaluation:  11/09/98

Tel:  (303) 684-8436

 

E-mail:  jwcsys@aol.com  

URL:  www.caldwellsys.com

 

 