|
Issue Date: March 31,
2006
Caldwell Systems Corp.
Tank Manager
Monitoring Systems with CITLDS
(Ultrasonic
Probe)
CONTINUOUS IN-TANK
LEAK DETECTION METHOD
(CONTINUOUS AUTOMATIC TANK GAUGING)
|
Certification |
Leak
rate of 0.2 gph with PD = 100% and PFA = 0%. |
|
Leak Threshold |
Not
applicable for qualitative methods.
Method is qualitative and reports a result of “pass” or “fail”. |
|
Applicability |
Gasoline, diesel, aviation fuel, solvents, waste oil, fuel oil #4, water.
Other liquids with known coefficients of expansion and density may be tested
after consultation with the manufacturer. |
|
Tank Capacity |
Maximum of 18,000 gallons for single tanks
Maximum of 54,000 gallons cumulative capacity for manifolded tank systems.
Minimum product level required to conduct a test is 20 inches. |
|
Throughput |
Monthly maximum of 147,136 gallons. |
|
Waiting Time |
Minimum of 4 hours stabilization time is allowed between delivery and data
collection. |
|
Test Period |
Data
collection time ranges from 3 to 27 days.
Data sampling frequency is every 1 minute.
System collects data at naturally occurring product levels without
interfering with normal tank operation, and discards data from unstable
periods when system performs test. |
|
Temperature |
Average for product is determined by a minimum of 5 sensors. |
|
Water Sensor |
Must
be used to detect water ingress.
Minimum detectable water level in the tank is 0.736 inch.
Minimum detectable change in water level is 0.031 inch. |
|
Calibration |
Probe
must be checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
|
Comments |
Evaluated using both single and manifolded tank systems with probes in each
tank.
For valid monthly testing, a conclusive test report must be produced for
each tank every month.
System warns operator if there are no “passing” tests completed during the
month.
For very active tanks, a tank shut down may become necessary in order for
the system to collect enough quiet-time data for a test.
Constant and variable leaks were mathematically induced into tight tank test
records, which were collected by systems installed at various active tank
sites.
The database for evaluation of the system included sites with vapor recovery
and blending dispensers.
Tanks used in this evaluation contained gasoline and diesel. |
|
Caldwell
Systems Corp.
|
Evaluator:
Ken Wilcox Associates
|
|
600 South
Sunset Street, Unit D
|
Tel:
(816) 443-2494
|
|
Longmont, CO
80501
|
Date of Evaluation: 04/08/05
|
|
Tel: (303)
684-8436
|
|
|
E-mail:
jwcsys@aol.com |
|
|
URL:
www.caldwellsys.com
|
|
|