Issue Date: August 7, 2017

Revision Date:  September 30, 2020

Franklin Fueling Systems

Incon TS-1001/2001, TS-5, TS-550, TS-5000, TS-550evo, TS-5000evo, EVO 400, EVO 200,
S940 Alarm Console, EVO 600, and EVO 6000 Consoles with FMP-ULS Universal Liquid
Sensor, FMP-UHS Universal Hydrostatic Sensor, FMP-ULS-C Universal Liquid Sensor
Chemical, FMP-ULS-PS Universal Liquid Sensor Position Sensitive sensors

INTERSTITIAL DETECTOR (LIQUID-PHASE)
 

Detector:

 

Output Type: qualitative
Sampling Frequency: continuous

Operating principle:

float/reed switch

 

Test Results:

 

unleaded gasoline

 

diesel*

 

biodiesel*

 


water

E85

brine
FMP-ULS            

Detection time (min)

<1

<1

<1

<1
<1
 

Fall time (min)

<1

<1

<1

<1
<1
 

Threshold Level (in)

1.0155

0.9944

0.9925

0.8775
1.0198
 
FMP-UHS            
Detection time (min)
<1
<1
<1
<1
<1
<1
Fall time (min)
<1
<1
<1
<1
<1
<1

Threshold Level (in)

0.9602

0.9144

0.9218

0.9397
0.9397
0.7561
FMP-ULS-PS            
Detection time (min)
<1
<1
<1
<1
<1
 
Fall time (min)
<1
<1
<1
<1
<1
 

Threshold Level (in)

1.4915

1.4882

1.4758

1.3770
1.4962
 
             
 
Lubrizol**
Afton**        
FMP-ULS-C            
Detection time (min)
<1
<1
       
Fall time (min)
<1
<1
       

Threshold Level (in)

1.1707

1.1281

       
FMP-ULS-PS            
Detection time (min)
<1
<1
       
Fall time (min)
<1
<1
       

Threshold Level (in)

1.4959

1.4290

       
             
 

*Evaluations determined these sensors' responses to the liquids shown above. Biodiesel blends B6-B20 meeting ASTM D7467 and biodiesel B100 meeting ASTM D6751 would also produce an alarm if the sensor threshold is exceeded. Responses to these fuels were not determined but would be expected to be very similar to the diesel responses.
** Manufacturer and evaluator claim that responses to Lubrizol 9888 and 9888C would be expected to be very similar to each other. Responses to Afton OTR 8332G. and OTR 8843G would be expected to be very similar to each other.

Comments:
Ken Wilcox Associates (KWA) has previously evaluated these sensors on one or more Franklin Fueling Systems ATG consoles. Results from the alarm functionality testing with the EVO600 and EVO6000 consoles have been combined with previously evaluated sensor threshold data performed by KWA.
Sensor TSP-UHS is the same as the TSP-ULS sensor except that the float has been inverted so that it may be used to monitor the brine reservoir of containment sumps. An alarm condition will occur when the fluid level drops below the end of the sensor. The FMP-ULS-PS is a position sensitive float switch that issues an alarm if not installed properly at the bottom of the intestinal or sump. Sensors are reusable.

 

 

Franklin Fueling Systems

Evaluator:  Ken Wilcox Associates

3760 Marsh Road

Tel:  (816) 443-2494

Madison, WI  53718

Dates of Evaluations:  05/02/2017, 11/08/18

Tel:  (800) 225-9787

 
E-mail:  info@franklinfueling.com  

URL:  www.franklinfueling.com

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.