Issue
Date: November 23, 2010
Leighton
O'Brien Technologies,
Ltd.
Qualitative Dry Line Test PM2 (for Rigid and Flexible
Pipelines)
LINE TIGHTNESS TEST
METHOD
|
Certification |
Leak
rate of 0.1 gph with PD = 100% and PFA = 0%. |
|
Leak Threshold |
< 0.05
gph. Proprietary for dry test mode. |
|
Applicability |
Gasoline, diesel, aviation fuel, fuel oil #4, biodiesel B6-B20 meeting ASTM
D7647 biodiesel B100 meeting ASTM D6751*.
Pipelines containing other liquids may be tested after approval from the
manufacturer.
Lines can be tested either empty or
partially filled with liquid.
*NWGLDE Listings apply to
leak detection functionality only and not material compatibility -
see "Disclaimer". |
|
Specification |
System
tests fiberglass, steel and flexible pipelines.
Dry Tests are conducted at 45 psi or 150% of operating pressure using the
system as a digital manometer against the fluid and trapped vapor in the
pipeline.
Mechanical line leak detector must be removed or manually isolated from
pipeline for duration of test, or if testing is to be conducted with
mechanical line leak detector in place, check valve in pump must be manually
closed. |
|
Pipeline Capacity |
Maximum
of 371.22 gallons in rigid piping.
Maximum of 109.8 gallons in flexible piping.
Maximum total of 481
gallons in combination rigid and flexible (the capacity of the flexible
component cannot exceed 109.8 gallons).
Manifolded piping may be
tested as long as the total length of piping is within the capacity and
configuration limitations.
|
|
Waiting Time |
None
between delivery and testing.
None between dispensing and testing. |
|
Test Period |
Under ideal conditions, 3 minutes after
installing in line.
Test data is collected
continuously and recorded by computer.
Data is analyzed at the
Leighton O'Brien analysis center with telemetry. |
|
Calibration |
No temperature sensors used.
System must be calibrated
yearly in accordance with manufacturer's instructions. |
|
Comments |
Groundwater is overcome with pressure on the top of the fluid test system
apparatus during the dry test. |
|
Leighton O'Brien
Technologies, Ltd. |
Evaluator:
Ken Wilcox Associates |
|
Suite 1/96 Camberwell Road |
Tel:
(816) 443-2494 |
|
Hawthorn East, Victoria,
Australia 3123 |
Date of Evaluation:
10/11/10 |
|
Tel: +61(03)
9813 5122 |
|
|
E-mail: enquiry@leightonobrien.com |
|
|
URL: http://www.leightonobrien.com |
|
|