Issue Date: April 18, 1997
Revision Date: August 10, 2001

Pneumercator Company, Inc.

LC 1000 Series, E-14-29, E-700-1, LDE-700, LDE-740, TMS 2000, TMS 3000 with
Level Sensor Models LS600AB, LS600LDBN, LS610, RSU800

INTERSTITIAL DETECTOR (LIQUID-PHASE)

 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

float switch

Test Results:

unleaded gasoline

diesel

water

LS600AB

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Lower detection limit (in)

3.32

3.28

3.18

LS600LDBN

 

 

 

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Lower detection limit (in)

0.99

0.97

0.87

LS610

 

 

 

Detection time (sec)

<1

<1

<1

Fall time (sec)

<1

<1

<1

Lower detection limit (in)

0.44

0.43

0.42

RSU800 (low level)

 

 

 

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Lower detection limit (ppm)

2.57

2.53

2.31

RSU800 (high level)

 

 

 

Detection time (min)

<1

<1

<1

Fall time (min)

<1

<1

<1

Lower detection limit (ppm)

13.31

13.24

13.01

Specificity Results:
Manufacturer and evaluator claim sensor will respond to any liquid.

Comments:
Sensors are reusable.

 

Pneumercator Company, Inc.

Evaluator:  Ken Wilcox Associates

120 Finn Court

Tel:  (816) 443-2494

Farmingdale, NY 11735

Date of Evaluation:  01/22/96

Tel:  (631) 293-8450

(Revised 03/02/01)

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.