Issue Date: November 22, 1995
Revision Date: January 11, 2001

Pneumercator Company, Inc.

LDE 700, LDE 740, LDE 9000 with Sensor Probe Models 9-901, 9-902, 9-903

INTERSTITIAL DETECTOR (LIQUID-PHASE)

 

Detector:

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

capacitance

Test Results:

 

unleaded gasoline

synthetic gasoline

Detection time (sec)

<1

<1

Fall time

manual reset

manual reset

Lower detection limit (cm)

 

 

    9-901

0.32

0.36

    9-902

0.36

0.34

    9-903

0.76

0.74

Specificity Results (in addition to above):
Activated:  n-hexane, diesel, jet-A fuel, toluene, xylene(s), water.

Comments:
Sensors are reusable.
Capacitance probes do not work with oxygenated fuels.

 

Pneumercator Company, Inc.

Evaluator:  Ken Wilcox Associates

120 Finn Court

Tel:  (816) 443-2494

Farmingdale, NY 11735

Date of Evaluation:  12/14/93

Tel:  (631) 293-8450

 