Issue Date: November 22, 1995
Revision Date: March 11, 2004
Vaporless Manufacturing
Vaporless
LD-3000, LD-3000S
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
|
Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
|
Leak Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
|
Applicability |
Gasoline, diesel,
aviation fuel.
Other liquids may be tested after consultation with the manufacturer.
|
|
Specification |
System tests
pressurized steel and fiberglass pipelines.
Tests are conducted at operating pressure. |
|
Pipeline Capacity |
Maximum of 320
gallons. |
|
Waiting Time |
None between
dispensing and testing. |
|
Test Period |
Response time is
9 seconds. |
|
System Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
LD3000 - restricted flow to dispenser if leak is declared.
LD3000S - pump shutoff if leak is declared. |
|
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
|
Comments |
Functionality and
operability of the 99 LD-3000 are unchanged by installation of the Leak
Detection Sensor (piston switch) that supports the VMI ISM-4080 and ISM-4081
Integrated Shutdown Module. |
|