Issue Date: November 22, 1995
Revision Date: May 15, 2008
Veeder-Root
TLS 350,
350PC, 350R, 350RPC, 350Plus, 450, Red Jacket ProMax Leak Detector,
Series 8484
AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR
|
Certification |
Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA
= 0%.
*Since leak
rate varies as a function of pressure, this leak rate and pressure were
certified using an equivalent leak rate and pressure, in accordance with an
acceptable protocol. |
|
Leak Threshold |
1.88 gph for leak
rate of 3.0 gph.
0.17 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
|
Applicability |
Gasoline, diesel,
aviation fuel.
Other liquids may be tested after consultation with the manufacturer.
|
|
Specification |
System tests
pressurized fiberglass and steel pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector installed in
the pipeline. |
|
Pipeline Capacity |
Maximum of 98.4
gallons. |
|
Waiting Time |
None between
delivery and testing.
Minimum of 16 minutes between dispensing and testing for leak rate of 3.0
gph.
Minimum of 45 minutes to 1 hour between dispensing and testing for leak rate
of 0.2 gph.
Minimum of 2 hours, 30 minutes between dispensing and testing for leak rate
of 0.1 gph. |
|
Test Period |
Response time is
28.8 seconds for leak rate of 3.0 gph.
Response time is 32 to 48 minutes for leak rate of 0.2 gph.
Response time is 18 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
|
System Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm activation if leak is
declared. |
|
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
|
Veeder-Root |
Evaluator: Midwest Research Institute |
|
125
Powder Forest Dr. |
Tel:
(816) 753-7600 |
|
Simsbury,
CT 06070-2003 |
Dates of
Evaluations: 08/07/91, 12/18/96 |
|
Tel:
(860) 651-2700 |
Evaluator: Ken Wilcox
Associates |
|
E-mail:
info@veeder.com |
Tel: (816)
443-2494 |
|
URL: www.veeder.com |
Date of Evaluation:
02/27/08 |
|