|
Issue Date: June 2, 1998
Revision Date:
May 15, 2008
Veeder-Root
TLS 350,
350PC, 350R, 350RPC, 350Plus, 450, LLD-300, Red Jacket ProMax Leak Detector, Series 8484
(for Flexible Pipelines)
AUTOMATIC ELECTRONIC LINE LEAK
DETECTOR
|
Certification |
Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
Leak rate of 0.2 gph at operating pressure with PD = 100% and PFA = 0%.
Leak rate of 0.1 gph at 1.5 times operating pressure* with PD = 100% and PFA
= 0%.
*Since leak
rate varies as a function of pressure, this leak rate and pressure were
certified using an equivalent leak rate and pressure, in accordance with an
acceptable protocol. |
|
Leak Threshold |
1.5 gph for leak
rate of 3.0 gph.
0.17 gph for leak rate of 0.2 gph.
0.05 gph for leak rate of 0.1 gph.
A pipeline system should not be declared tight if the test result indicates
a loss that equals or exceeds this threshold. |
|
Applicability |
Gasoline, diesel,
aviation fuel.
Other liquids may be tested after consultation with the manufacturer.
|
|
Specification |
System tests
pressurized flexible pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector installed in
the pipeline. |
|
Pipeline Capacity |
Maximum of 40.8
gallons. |
|
Waiting Time |
None between
delivery and testing.
Minimum of 13 minutes between dispensing and testing for leak rate of 3.0
gph.
Minimum of 4 minutes to 1 hour, 9 minutes between dispensing and testing for
leak rate of 0.2 gph.
Minimum of 1 to 4 hours between dispensing and testing for leak rate of 0.1
gph. |
|
Test Period |
Response time is
1 to 6 minutes for leak rate of 3.0 gph.
Response time is 40 minutes to 1 hour for leak rate of 0.2 gph.
Response time is 45 minutes to 1 hour, 15 minutes for leak rate of 0.1 gph.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
|
|
System Features |
Permanent
installation on pipeline.
Automatic testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm activation if leak is
declared. |
|
Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
|
Veeder-Root |
Evaluator: Midwest Research Institute |
|
125
Powder Forest Dr. |
Tel:
(816) 753-7600 |
|
Simsbury,
CT 06070-2003 |
Dates of
Evaluations: 10/16/95, 01/31/97 |
|
Tel:
(860) 651-2700 |
Evaluator: Ken Wilcox
Associates |
|
E-mail:
info@veeder.com |
Tel: (816)
443-2494 |
|
URL: www.veeder.com |
Date of Evaluation:
02/27/08 |
|