Issue Date: June 5, 1998
Revision Date:  November 9, 1998

Veeder-Root

Dispenser Pan Sensor 847990-001 and Differentiating Dispenser Pan Sensor 847990-002 with
Dispenser Control Interface

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:         

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

product permeable, reed switch/float

 Test Results:

 

polymer strip

float switch

 

unleaded gasoline

diesel

water

Dispenser Pan Sensor 847990-001

     

Detection time (sec)

<1

<1

<1

Minimum product level (in)

1.71

1.66

1.62

Precision (in)

0.006

0.004

0.008

Differentiating Dispenser Pan Sensor 847990-002

 

 

 

Minimum product thickness (in)

0.06

0.06

N/A*

Minimum product level (in)

0.03

0.06

6.39

Precision (in)

N/A**

N/A**

0.008

Detection time (min:sec)

06:30

19:50

<00:01

*See glossary.
**Tested at discrete levels only.

Specificity Results (in addition to above):
Activated:  synthetic gasoline, n-hexane, toluene, xylene(s)
Not activated:  water (polymer strip only)

Comments:
Sensors are reusable.
These sensors do not require a console.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT  06070-2003

Dates of Evaluations:  11/15/93, 11/02/98

Tel:  (860) 651-2700

 

 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.