Issue Date: November 22, 1995
Revision Date: June 20, 2008

Veeder-Root

ILS-350, TLS-300C, 300i, 300PC, 350, 350PC, 350R, 350RPC, TLS-450 Series, Red Jacket ProMax and ProPlus
with Solid-State Pan/Sump Sensor 794380-321, 351,
Piping Sump Sensor 794380-208, 209,
Micro Sensor 794380-340

INTERSTITIAL DETECTOR (LIQUID-PHASE)

Detector:         

Output type:

qualitative

Sampling frequency:

continuous

Operating principle:

product permeable, ultrasonic/float switch

 

Test Results:

 

unleaded gasoline

diesel

water

Solid-State Pan/Sump Sensor 794380-321, 351

 

 

 

Minimum product thickness (cm)

2.60

2.50

2.60

Precision (cm)

0.010

0.010

0.010

Detection time (sec)

<1

<1

<1


Piping Sump Sensor 794380-208, 209

     

Minimum product level (cm)

3.51

3.40

3.03

Precision (cm)

0.011

0.011

0.011

Detection time (sec)

<1

<1

<1


Micro Sensor 794380-340*

 

 

 

Minimum product thickness (cm)

0.51

0.46

0.48

Precision (cm)

0.011

0.007

0.007

Detection time (sec)

<1

<1

<1

Comments:
Sensors are reusable.
208 and 209 sensors are also compatible with 300 series.
Comparison of TLS-450 with TLS-350 series console showed comparable results when evaluated with representative sensors.
* Micro Sensor 794380-340 is not supported by TLS 450 series console.
 

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT  06070-2003

Dates of Evaluations: 10/20/94, 05/22/02, 03/03/08

Tel:  (860) 651-2700

 

E-mail: dhalla@veeder.com  
URL: www.veeder.com/dynamic/index.cfm  
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.