Issue Date: November
22, 1995
Revision Date: June 20, 2008
Veeder-Root
ILS-350, TLS-300C, 300i, 300PC, 350,
350PC, 350R, 350RPC, TLS-450 Series, Red Jacket ProMax and ProPlus
with
Solid-State Pan/Sump Sensor 794380-321, 351,
Piping Sump Sensor 794380-208, 209,
Micro Sensor 794380-340
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
|
Output type: |
qualitative |
|
Sampling
frequency: |
continuous |
|
Operating
principle: |
product permeable, ultrasonic/float switch |
Test Results:
|
|
unleaded gasoline |
diesel |
water |
|
Solid-State Pan/Sump Sensor 794380-321, 351 |
|
|
|
|
Minimum
product thickness (cm) |
2.60 |
2.50 |
2.60 |
|
Precision (cm) |
0.010 |
0.010 |
0.010 |
|
Detection time (sec) |
<1 |
<1 |
<1 |
|
Piping Sump Sensor 794380-208, 209 |
|
|
|
|
Minimum
product level (cm) |
3.51 |
3.40 |
3.03 |
|
Precision (cm) |
0.011 |
0.011 |
0.011 |
|
Detection time (sec) |
<1 |
<1 |
<1 |
|
Micro
Sensor 794380-340* |
|
|
|
|
Minimum
product thickness (cm) |
0.51 |
0.46 |
0.48 |
|
Precision (cm) |
0.011 |
0.007 |
0.007 |
|
Detection time (sec) |
<1 |
<1 |
<1 |
Comments:
Sensors are reusable.
208 and 209 sensors are also compatible with 300 series.
Comparison of TLS-450 with TLS-350 series console showed comparable results when
evaluated with representative sensors.
* Micro Sensor 794380-340 is not supported by TLS 450 series console.
|
Veeder-Root |
Evaluator: Ken Wilcox Associates |
|
125
Powder Forest Dr. |
Tel:
(816) 443-2494 |
|
Simsbury, CT 06070-2003 |
Dates of
Evaluations: 10/20/94, 05/22/02, 03/03/08 |
|
Tel:
(860) 651-2700 |
|
|
E-mail: dhalla@veeder.com |
|
|
URL: www.veeder.com/dynamic/index.cfm |
|
|