Issue Date: December
7, 2001
Revision Date: June 20, 2008
Veeder-Root
TLS-350, 350R Series, TLS-450
Series, Red Jacket
ProMax with
Discriminating
Interstitial Sensor 794380-343, Micro Sensor 794380-344
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
|
Output type: |
qualitative, discriminating (794380-343), non-discriminating (794380-344) |
|
Sampling
frequency: |
continuous |
|
Operating
principle: |
optical sensor and conductivity
(794380-343), optical sensor (794380-344) |
Test Results:
|
|
unleaded gasoline |
diesel |
water |
|
Discriminating Interstitial
Sensor 794380-343 |
|
|
|
|
Detection time (min) |
<1 |
<1 |
<1 |
|
Fall
time (min) |
<1 |
<1 |
<1 |
|
Lower
detection limit (in) |
<0.1 |
<0.1 |
<0.1 |
|
|
unleaded gasoline |
diesel |
water |
E85 |
|
Micro
Sensor 794380-344 |
|
|
|
|
|
Detection time (min) |
<1 |
<1 |
<1 |
<1 |
|
Fall
time (min) |
<1 |
<1 |
<1 |
<1 |
|
Lower
detection limit (in) |
<0.1 |
<0.1 |
<0.1 |
<0.1 |
Specificity Results:
Evaluator
claims both 794380-343 and 794380-344 sensors will respond in any liquid after
the sensor threshold is exceeded.
Sensor 794380-343 is designed to discriminate between product and water.
Separate alarms are designed to be triggered for product and water.
Manufacturer’s Specifications:
Sensors
794380-343 and 794380-344 can be removed, cleaned, and reinstalled, for periodic
testing, if an alarm is triggered or if service is necessary.
Sensor 794380-343 has no moving parts.
Sensor 794380-344 can be easily removed, cleaned, and reinstalled if an alarm is
triggered or for periodic testing.
Sensor 794380-344 is designed for use in contained risers and the interstitial
space of double-wall steel tanks. When product or an open sensor (referred to
as “Sensor Out”) is detected, an audible alarm is actuated, a message is
displayed on the TLS-350 or TLS-350R console, and a printed message is generated
if the console is equipped with a printer. The alarms are also recorded as part
of the TLS-350 or TLS-350R “Alarm History Report”.
Comparison of TLS-450 with TLS-350 series console showed comparable results when
evaluated with representative sensors.
|
Veeder-Root |
Evaluator: Ken Wilcox Associates |
|
125
Powder Forest Dr. |
Tel:
(816) 443-2494 |
|
Simsbury, CT 06070-2003 |
Dates of
Evaluations: 05/10/01, 02/02/06, 03/03/08 |
|
Tel:
(860) 651-2700 |
|
|
E-mail: dhalla@veeder.com |
|
|
URL: www.veeder.com/dynamic/index.cfm |
|
|