Issue Date: December 23, 2002
Revision Date: May 15, 2008

Veeder-Root

TLS 350, 350PC, 350R, 350RPC, 350Plus, 350J, 450, Red Jacket ProMax
Line Leak Detector, Series 8484, Software Version X19 or Higher
(for Rigid and/or Flexible Pipelines)

AUTOMATIC ELECTRONIC LINE LEAK DETECTOR

Certification

Leak rate of 3.0 gph at 10 psi* with PD = 100% and PFA = 0%.
*Since leak rate varies as a function of pressure, this leak rate and pressure were certified using an equivalent leak rate and pressure, in accordance with an acceptable protocol.

Leak Threshold 2.0 gph.
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel, ethanol blends (with gasoline) between 0% and 98%*, absolute ethanol (100%)*, biodiesel and biodiesel blends (with diesel)*.
Other liquids may be tested after consultation with the manufacturer.
*NWGLDE Listings apply to leak detection functionality only and not material compatibility – see “Disclaimer."
Specification System tests pressurized rigid, flexible, and combinations of rigid and flexible pipelines.
Tests are conducted at operating pressure.
System will not function with a mechanical line leak detector installed in the pipeline.
Pipeline Capacity Maximum of 212 gallons.
Waiting Time None between delivery and testing.
None between dispensing and testing.
Test Period Response time is 1 to 6 minutes.
Test data are acquired and recorded by a microprocessor.
Calculations are automatically performed by the microprocessor.
System Features Permanent installation on pipeline.
Automatic testing of pipeline. Preset threshold.
Single test to determine if pipeline is leaking.
Pump shutdown (optional), message display and alarm activation if leak is declared.
Calibration System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments System was evaluated on a pipeline consisting of rigid and flexible piping, and the resulting combined bulk modulus was determined by physical measurement at evaluator’s facility.
To use this system, a measurement of bulk modulus must be made at the owner's facility so that the software can be programmed to deal with the specific characteristics of the piping system at the facility.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT  06070-2003

Dates of Evaluations:  08/19/02, 02/27/08

Tel:  (860) 651-2700

 

E-mail:  info@veeder.com  
URL:  www.veeder.com  
 

 | Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary |

Appearance on this list is not to be construed as an endorsement by any regulatory agency nor is it any guarantee of the performance of the method or equipment.
Equipment should be installed and operated in accordance with all applicable laws and regulations.  For full details, please refer to our expanded "DISCLAIMER" page.