Issue
Date: July 8, 2003 Veeder-Root ILS-350, TLS-300 Series, TLS 350
Series, TLS-450 Series, EMC Series, EMC Basic, Red Jacket ProMax and ProPlus
|
|
Output type: |
qualitative, non-discriminating |
|
Sampling frequency: |
continuous |
|
Operating principle: |
float switch |
Test Results:
|
Position Sensitive Sensor 794380-323 |
unleaded gasoline |
diesel |
water |
E85 |
|
Detection time (min) |
<1 |
<1 |
<1 |
<1 |
|
Fall time (min) |
<1 |
<1 |
<1 |
<1 |
|
Product activation height (in) |
1.520 |
1.449 |
1.359 |
1.479 |
Specificity Results:
Evaluator reports this sensor will
respond to any liquid once sensor’s threshold level has been exceeded.
This
testing included water, diesel fuel, gasoline, and E85.
Manufacturer’s Specifications:
Sensor is reusable.
Comments:
Sensor will
alarm if it is raised from the bottom of the containment vessel.
Comparison of TLS-450 with TLS-350 series console showed comparable results when
evaluated with representative sensors.
|
Veeder-Root |
Evaluator: Ken Wilcox Associates |
|
125 Powder Forest Dr. |
Tel: (816) 443-2494 |
|
Simsbury, CT 06070-2003 |
Dates of Evaluations: 04/08/03, 02/02/06, 03/03/08 |
|
Tel: (860) 651-2700 |
|
| E-mail: dhalla@veeder.com | |
| URL: www.veeder.com/dynamic/index.cfm |
|
| Home | Vendors: A - F | Vendors: G - M | Vendors: N - S | Vendors: T - Z | Method Index | Glossary | Appearance on
this list is not to be construed as an endorsement by any regulatory agency nor