Issue Date: November 22, 1995
Revision Date: February 6, 2006
Veeder-Root
(originally listed as Marley Pump Co.)
Red Jacket
FX1, FX2
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
| Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
| Leak
Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
| Applicability |
Gasoline, diesel,
aviation fuel.
Other liquids may be tested after consultation with the manufacturer. |
| Specification |
System tests
pressurized fiberglass and steel pipelines.
Tests are conducted at 8-12 psi. |
| Pipeline
Capacity |
Maximum of 316
gallons for FX1.
Maximum of 362 gallons for FX2. |
| Waiting
Time |
None between
delivery and testing.
None between dispensing and testing.
Stabilization time up to 45 minutes may be required after dispensing when
temperature extremes are present. |
| Test
Period |
Response time is
less than 5 minutes. |
| System
Features |
Permanent
installation on pipeline.
Automatic testing of pipeline. Preset threshold.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. |
| Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
|
Veeder-Root
|
Evaluator:
Ken Wilcox Associates
|
|
125 Powder Forest Dr.
|
Tel: (816) 443-2494
|
|
Simsbury, CT 06070-2003
|
Dates of Evaluations: 03/14/94,
06/01/94
|
|
Tel: (860) 651-2700
|
|
|
E-mail:
aabri@veeder.com |
|
|
URL: www.veeder.com/dynamic/index.cfm |
|
|