Issue Date: November 22, 1995
Revision Date: February 6, 2006

Veeder-Root
(originally listed as Marley Pump Co.)

Red Jacket FX1, FX2, Flexline
(for Flexible Pipelines)

AUTOMATIC MECHANICAL LINE LEAK DETECTOR

Certification Leak rate of 3.0 gph with PD = 100% and PFA = 0%.
Leak Threshold 2.0 gph. 
A pipeline system should not be declared tight if the test result indicates a loss that equals or exceeds this threshold.
Applicability Gasoline, diesel, aviation fuel. 
Other liquids may be tested after consultation with the manufacturer.
Specification System tests pressurized flexible pipelines.
Pipeline Capacity Maximum of 49 gallons.
Waiting Time None between delivery and testing. 
None between dispensing and testing.
Test Period Response time is less than 3 minutes.
System Features Permanent installation on pipeline. 
Automatic testing of pipeline. Preset threshold. 
Single test to determine if pipeline is leaking. 
Restricted flow to dispenser if leak is declared.
Calibration System must be checked annually and, if necessary, calibrated in accordance with manufacturer's instructions.
Comments Enviroflex pipeline with a bulk modulus* of 1,280 psi was used during this evaluation. 
To perform a valid test, time delays must be integrated into electronic dispensing equipment or retrofitted in junction box. Without this delay, there is no guarantee that a nozzle will be closed for sufficient time to allow leak detector to perform pipeline test and provide uninterrupted service. 
*See glossary.

 

Veeder-Root

Evaluator:  Ken Wilcox Associates

125 Powder Forest Dr.

Tel:  (816) 443-2494

Simsbury, CT 06070-2003

Date of Evaluation:  03/22/94

Tel: (860) 651-2700

 

E-mail:  aabri@veeder.com  
URL:  www.veeder.com/dynamic/index.cfm  
 