Issue Date: July 31, 2001
Revision Date: April 15, 2002
Veeder-Root
(originally listed as Marley Pump Co.)
Red Jacket
FX1DV, FX2DV Installed in the Big-Flow
(for Flexible Pipelines)
AUTOMATIC MECHANICAL LINE LEAK
DETECTOR
| Certification |
Leak rate of 3.0
gph with PD = 100% and PFA = 0%. |
| Leak
Threshold |
2.0 gph.
A pipeline system should not be declared tight if the test result
indicates a loss that equals or exceeds this threshold. |
| Applicability |
Diesel. |
| Specification |
System tests
pressurized flexible pipelines.
Tests are conducted at operating pressure. |
| Pipeline
Capacity |
Maximum of 39.4
gallons. |
| Waiting
Time |
None between
delivery and testing.
None between dispensing and testing. |
| Test
Period |
Response time is
less than 3 minutes. |
| System
Features |
Permanent
installation on pipeline.
Automatic hourly testing of pipeline.
Preset threshold.
Single test to determine if pipeline is leaking.
Restricted flow to dispenser if leak is declared. |
| Calibration |
System must be
checked annually and, if necessary, calibrated in accordance with
manufacturer's instructions. |
|
Veeder-Root
|
Evaluator:
Ken Wilcox Associates
|
|
125 Powder Forest Dr.
|
Tel: (816) 443-2494
|
|
Simsbury, CT 06070-2003
|
Dates of Evaluations:
03/15/94,
07/30/96, 03/11/99
|
|