Issue Date: November 14, 1997
Revision Date: April 15, 2002
Veeder-Root
(originally listed as Marley Pump Co.)
Red
Jacket Electronics RE400-058-5, RE400-059-5,
RE400-147-5,
RE400-148-5 Overfill Sensor, RE400-111-5 Sump Sensor, RE400-203-5 Optical Liquid Discrimination Sensor,
RE400-204-5 Dispenser
Pan Monitor, RE400-180-5 Liquid Refraction Sensor
INTERSTITIAL DETECTOR (LIQUID-PHASE)
Detector:
|
Output
type: |
qualitative
|
|
Sampling
frequency: |
continuous
|
|
Operating
principle: |
float
switch (RE400-058-5, RE400-059-5, RE400-147-5, RE400-148-5 Overfill
Sensor, RE400-111-5 Sump Sensor),
electrical conductivity
and optical (RE400-203-5 Optical Liquid Discrimination Sensor),
conductive polymer
(RE400-204-5 Dispenser Pan Monitor),
optical
(RE400-180-5 Liquid Refraction Sensor) |
Test
Results:
|
RE400-058-5,
RE400-059-5, RE400-147-5, RE400-148-5 Overfill Sensor
|
unleaded
gasoline
|
diesel
|
water
|
|
Detection
time (sec)
|
<1
|
<1
|
<1
|
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
|
Lower
detection limit (cm)
|
2.97
|
2.82
|
2.57
|
|
RE400-111-5
Sump Sensor
|
|
|
|
|
Detection
time (sec)
|
<1
|
<1
|
<1
|
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
|
Lower
detection limit (cm)
|
3.60
|
3.41
|
3.20
|
|
RE400-203-5
Optical Liquid Discrimination Sensor
|
|
|
|
|
Detection
time (sec)
|
<1
|
<1
|
<1
|
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
|
Lower
detection limit (cm)
|
1.17
|
1.12
|
1.10
|
|
RE400-204-5
Dispenser Pan Monitor
|
|
|
|
|
Detection
time (hr:min:sec)
|
<00:30:00
|
<02:00:00
|
<00:00:01
|
|
Fall
time (hr:min:sec)
|
<01:20:00
|
1-2
days
|
<00:00:01
|
|
Lower
detection limit (cm)
|
0.44
|
0.44
|
1.08
|
|
RE400-180-5
Liquid Refraction Sensor
|
|
|
|
|
Detection
time (sec)
|
<1
|
<1
|
<1
|
|
Fall
time (sec)
|
<1
|
<1
|
<1
|
|
Lower
detection limit (cm)
|
1.17
|
1.12
|
1.10
|
Specificity
Results (in addition to above):
Activated:
synthetic gasoline, n-hexane,
jet-A fuel, toluene, xylene(s).
Comments:
Evaluator
claims sensors will respond to any liquid once threshold has been exceeded.
After
exposure to diesel, RE400-204-5 Dispenser
Pan Monitor reading may not return to pre-contaminated level.
Sensors
are reusable.
|
Veeder-Root
|
Evaluator:
Ken Wilcox Associates
|
|
125 Powder Forest Dr.
|
Tel: (816) 443-2494
|
|
Simsbury, CT 06070-2003
|
Date of Evaluation:
06/01/95
|
|
Tel: (860) 651-2700
|
|
|