Search NWGLDE.org   
           



           
  METHOD INDEX


Revision Date:  September 9, 2016
 

Continuous In-Tank Leak Detection Method
(Continuous Automatic Tank Gauging)

Click on the vendors specific EQUIPMENT NAME to go to that Listing.


  VENDOR

  EQUIPMENT NAME

LEAK RATE/THRESHOLD/
MAX TANK CAPACITY

Dover Fueling Solutions ProGauge MagLink LX ATG with CSLD (924B and DMP Magnetostrictive Probes) 0.2 gph/0.1 gph (single tanks), 0.1 gph (manifolded tanks)/25,215 gallons
Dresser Wayne Europe TIG 5000 ATG System
(Q0400-4xx Magnetostrictive Probe)
0.2 gph/0.1 gph/35,000 gallons
EBW, Inc.

AutoStik II, AutoStik Jr. with SCALD 2.0
(INCON TSP-LL2 Magnetostrictive Probe)

Certification for those sold on or after March 1, 2004

0.2 gph/0.1 gph/49,336 gallons
Franklin Fueling Systems

INCON T1 Series TS-750, TS-1000, TS-1001, TS-2000, TS-2001,

INCON T5 Series TS-5, TS-608, TS-550, TS-550 evo, TS-5000, TS-5000 evo,

Colibri CL6 & TS-CL6 Series with SCALD 2.0

(INCON TSP-LL2 and FMP-LL3 Magnetostrictive Probe)

0.2 gph/0.1 gph/49,336 gallons
Franklin Fueling Systems INCON T5 Series, TS-5, TS-550, TS-5000, TS-550evo and TS-5000evo, Colibri, EVO 200, EVO 400, EVO 600 and EVO 6000 consoles with SCALD 3 (INCON TSP-LL2 and FMP-LL3 Magnetostrictive Probe) 0.2 gph/0.16-0.17 gph (single tanks),
0.135-0.155 gph (manifolded tanks)/32,891 gallons
Hectronic GmbH Hectronic Optilevel Dynamic Leak Detection System, Optilevel CITLDS (Capacitance Probe) 0.2 gph/0.1 gph/11,869 gallons (single tanks),
23,778 gallons (manifolded tanks)
OMNTEC Mfg., Inc. OEL 8000 II, K-OEL 8000 II, OEL 8000 III (Proteus Series-B, K and X) Monitoring System with CITLDS
(MTG-XX Magnetostrictive Probe)
0.2 gph/0.1 gph/18,000 gallons
OPW Fuel Management Site Sentinel Model iSite and Site Sentinel Integra with SLD Version 1 (Model 924B Magnetostrictive Probes with 2 inch dia or 4 inch dia Floats or Q0400-4xx Magnetostrictive Probe) 0.2 gph/0.1 gph/30,258 gallons (single tanks and manifolded tank groups up to 3 tanks)

OPW Fuel Management Systems
(originally listed as Emco Electronics, Tuthill Transfer Systems)

EECO System 1000,1000EG, 1500, 2000, 3000 and Galaxy ATG Systems (Q0400-4xx Magnetostrictive Probe or OPW 924/B TLM-B Magnetostrictive Probe)

0.2 gph/0.1 gph/35,000 gallons

Simmons Corp. (originally listed as Caldwell Systems Corp.)

Simmons/Caldwell Tank Manager Monitoring Systems with CITLDS (Ultrasonic Probe)

0.2 gph/N/A for qualitative methods/18,000 gallons

Veeder-Root Marconi (originally listed as Gilbarco Environmental Products and later as Marconi Commerce Systems)

EMC, EMC Basic, EMC Enhanced with CSLD,
PAO265XXXX100,
PA0300XXXX100
(Magnetostrictive Probe)

0.2 gph/0.16 gph (single tanks),
0.15 gph (manifolded tanks)/38,170 gallons

Veeder-Root 8600 Series and 8601 Series Consoles Monitoring Systems with CSLD (Model 8463 Series Probes) 0.2 gph/0.17 (single tank), 0.16 (manifold tanks); 58,752 gallons with monthly maximum throughput of 1,538.015 gallons. 98.6% PD/ <0.001 PFA

0.2 gph/0.15 (single tank), 0.15 (single tank), 0.12 manifold tanks) with monthly maximum throughput of 235,000 gallons. 99% PD/ <0.001 PFA

Veeder-Root

TLS-300i, 300J, 350, 350R, 350Plus, 450, Red Jacket ProMax and ProPlus Monitoring Systems with CSLD
(Models 8463, 8473, 8493 Magnetostrictive Probes)

0.2 gph/0.16 gph (single tanks), 0.15 gph (manifolded tanks)/38,170 gallons

 

 

| Top | Protocols | Checklists | Privacy | Glossary | Disclaimer |