VENDOR
|
EQUIPMENT NAME
|
LEAK RATE/THRESHOLD/
MAX PRODUCT SURFACE AREA
|
ASTTest
Services, Inc.
|
ASTTest
Mass Balance Leak Detection System
|
[(product
surface area in ft² ÷ 5,575 ft²) x 0.88 gph]/[(product
surface area in ft² ÷ 5,575 ft²) x 0.44 gph]/13,938 ft².
|
Engineering Design Group,
Inc.
|
EDG XLD 2000
Plus (Revision 1.02) Leak Detection System
(MTS DDA Magnetostrictive Probe) |
[(product surface area in ft² ÷
12,074 ft²) x 1.92 gph]/[(product surface area in ft² ÷ 12,074
ft²) x 0.96 gph]/12,076 ft². |
|
Ronan X-76 CTM
Automatic Tank Gauging System
(MTS Level Plus UST Probe) |
[(product surface area in ft² ÷ 564
ft²) x 0.2 gph]/[(product surface area in ft² ÷ 564 ft²) x 0.96
gph]/846 ft². |
Leak Detection Technologies
|
MDleak
Enhanced Leak Detection and Leak Location Method
|
0.005 gph/A tank should not
be declared tight when chemical marker is detected outside of
the tank/Not limited by capacity.
|
Mass
Technology Corp.
|
Precision Mass
Measurement Systems SIM-1000 and CBU-1000 (24 hour test)
|
[(product
surface area in ft² ÷ 1,257 ft²) x 0.1 gph]/[(product surface
area in ft² ÷ 1,257 ft²) x 0.05 gph]/
Not limited by product surface area.
|
|
Precision Mass
Measurement Systems SIM-1000 and CBU-1000 (48 hour test)
|
[(product
surface area in ft² ÷ 6,082 ft²) x 0.294 gph]/[(product
surface area in ft² ÷ 6,082 ft²) x 0.147 gph]/6,082 ft².
|
|
Precision Mass
Measurement Systems SIM-1000 and CBU-1000 (72 hour test)
|
[(product
surface area in ft² ÷ 14,200 ft²) x 0.638 gph]/[(product
surface area in ft² ÷ 14,200 ft²) x 0.319 gph]/Not
limited by product surface area.
|
Praxair Services, Inc.
(originally listed as Tracer Research, Corp.)
|
Tracer
ALD 2000 Automated Tank Tightness Test
|
0.1
gph/ A tank system should not be declared tight when tracer
chemical or hydrocarbon greater that the background level is
detected outside of the tank./Not limited by capacity.
|
Universal
Sensors and Devices, Inc.
|
LTC-1000
(Mass
Buoyancy Probe)
|
[(product
surface area in ft² ÷ 14,244 ft²) x 1.4 gph]/[(product
surface area in ft² ÷ 14,244 ft²) x 0.7 gph]/35,610 ft².
|
|
LTC-2000
(Differential Pressure Probe)
|
[(product
surface area in ft² ÷ 14,244 ft²) x 3.0 gph]/[(product
surface area in ft² ÷ 14,244 ft²) x 1.5 gph]/35,610 ft².
|
Varec, Inc.
(originally listed as Coggins Systems, Inc., and later as
Endress + Hauser Systems and Gauging)
|
FuelsManager and
Remote Terminal Unit RTU/8130 (MTS Magnetostrictive Probe)
|
[(product surface area in ft² ÷ 616 ft²) x 0.2 gph]/[(product
surface area in ft² ÷ 616 ft²) x 0.1 gph]/924 ft².
|
|
FuelsManager with
Barton Series 3500 ATG (48 hour test) (72 hour test)
|
[(product surface area in ft² ÷ 6,082 ft²) x 2.0 gph]/[(product
surface area in ft² ÷ 6,082 ft²) x 1.0 gph]/15,205 ft².
|
Varec, Inc. |
FuelsManager with
MTS M-Series ATG
(MTS Magnetostrictive Probe) |
[(product surface area in ft² ÷ 11,786 ft²) x
4.50 gph]/[(product surface area in ft² ÷ 11,786 ft²) x 2.25
gph]/ 11,786 ft² |
|
FuelsManager with
Enraf 854 ATG (Servo Buoyancy Probe) |
[(product surface area in ft² ÷ 11,786 ft²) x
3.00 gph]/[(product surface area in ft² ÷ 11,786 ft²) x 1.50
gph]/ 11,786 ft² |
Vista Precision Solutions, Inc. (originally listed as Vista Research, Inc. and Naval Facilities Engineering Service Center)
|
LRDP-24
(V1.0.2, V1.0.3)
|
[(product
surface area in ft² ÷ 6,082 ft²) x 2.0 or 3.0 gph]/[(product
surface area in ft² ÷ 6,082 ft²) x (2.0 or 3.0 gph - 0.223
gph)]/15,205 ft².
|
|
LRDP-48
(V1.0.2, V1.0.3)
|
[(product
surface area in ft² ÷ 6,082 ft²) x 2.0 or 3.0 gph]/[(product
surface area in ft² ÷ 6,082 ft²) x (2.0 or 3.0 gph - 0.188
gph)]/15,205 ft².
|
|
LRDP-24
(V1.1)
|
[(product
surface area in ft² ÷ 6,082 ft²) x 0.856 gph]/[(product
surface area in ft² ÷ 6,082 ft²) x 0.632 gph]/15,205 ft².
|
|
LRDP-48
(V1.1)
|
[(product
surface area in ft² ÷ 6,082 ft²) x 0.749 gph]/[(product
surface area in ft² ÷ 6,082 ft²) x 0.563 gph]/15,205 ft².
|