Click on the vendors specific EQUIPMENT NAME to go to that Listing.


  VENDOR

  EQUIPMENT NAME

LEAK RATE/THRESHOLD/
MAX PIPELINE CAPACITY

Estabrook EZY CHEK Systems (originally listed as Horner EZY CHEK)

EZY-Chek Manual Line Leak Detector
(for Rigid Pipelines)

0.1 gph/0.05 gph/426 gallons

  EZY-Chek Manual Line Leak Detector
(for Flexible Pipelines)
0.1 gph/0.05 gph/101 gallons

 

EZY-Chek II Automatic Line Leak Detector

0.1 gph/0.05 gph/129 gallons

Hansa Consult of North America, LLC HCNA Pipeline Leak Detection System, Version 2.1 0.068 gph/0.034 gph/5000 gallons
Leak Detection Technologies International MDleak Enhanced Leak Detection Method 0.005 gph/A Containment system should not be declared tight when chemical marker is detected outside of the pipeline system.  Not limited by capacity.
Leighton O'Brien Technologies, Ltd. Quantitative Wet Line Test PM2 (for Rigid and Flexible Pipelines) 0.1 gph/0.05 gph/371.22 gallons (Rigid), 109.8 gallons (Flexible), 481 gallons (combination)
  Qualitative Dry Line Test PM2 (for Rigid and Flexible Pipelines) 0.1 gph/0.05 gph/371.22 gallons (Rigid), 109.8 gallons (Flexible), 481 gallons (combination)
MassTech International, Ltd. ML3P Line Leak Detection System 0.1 gph/0.05 gph/172 gallons

Praxair Services, Inc.
(originally listed as Tracer Research, Corp.)

Tracer Tight Line Test

0.1 gph and 0.005gph/A pipeline system should not be declared tight when tracer chemical is detected outside of the pipeline/Not limited by capacity

ProTank, Inc.

LTH-5000 Line Tester

0.1 gph/0.05 gph/40 gallons

 

LTP-5000 Line Tester

0.1 gph/0.05 gph/41 gallons

Purpora Engineering, LLC (originally listed as Heath Consultants, Inc.)

Petro Tite Line Tester

0.1 gph/0.05 gph/129 gallons

 

Petro Tite Line Tester
(for Flexible Pipelines)

0.1 gph/0.05 gph/49.6 gallons

Tanknology

Proline Test Series III, Version 1.0

0.1 gph/0.05 gph/41 gallons

 

PTK-88

0.1 gph/0.05 gph/40 gallons

 

TLD-1

0.1 gph/0.05 gph/172 gallons

 

TLD-1
(Flexible Pipelines)

0.1 gph/0.05 gph/119.4 gallons

Training and Services Corp.
(originally listed as Hasstech)

AcuRite
(for Rigid and Flexible Pipelines)

0.1 gph/0.01 gph/150 gallons

Triangle Environmental, Inc.

TEI Model LT-3, Version 1.0

0.1 gph/0.05 gph/80 gallons

Western Environmental Resources

Model PLT-100R

0.1 gph/0.05 gph/80 gallons

 